Controls, Status indicators, Metering – Basler Electric IDP-1200 User Manual

Page 33

Advertising
background image

9437200990 Rev C

25

Figure 28. Output Control Screen

Controls

Controls include opening and closing of the ac (41A) breaker, selection of auto- or manual-mode
regulation, and adjustment of the generator voltage in Manual or Auto mode.

Control of the 41A breaker is provided through the AC Breaker button. When this button is pressed, Trip
and Close buttons will appear and enable the user to open and close the ac breaker.

Selection of auto- or manual-mode regulation is provided through the Mode Select button. When this
button is pressed, Put Reg in Auto and Put Reg in Manual buttons will appear and enable the user to
select either auto or manual regulation.

The 70BC-CS Manual button can be used to raise or lower the balance or manual reference. When the
button is pressed, Raise and Lower buttons will appear and enable the user to raise and lower the voltage
while operating in Manual mode.

Similarly, the 90DV-CS Auto button can be used to raise or lower the voltage while operating in Auto
mode.

Status Indicators

The System Status indicator displays the readiness of the control system channels.

The Channel in Control indicator displays which of the control system channels is actively controlling the
excitation level.

The Generator Breaker indicator displays whether the generator breaker is open or closed.

The Local/Remote indicator displays the local/remote control status of all control system channels. When
logged in with the Log In button and the proper password, this indicator is converted to a control button
that can be used to select either local or remote control. When pressed, Local Control and Remote
Control buttons appear and enable the user to select the operating mode. During proper operation, the
control mode of all channels should match. That is, all channels should be under local control or all
channels should be under remote control.

Metering

Metering indications are provided for generator voltage, current, watts, vars, and power factor. Metering
indications are also provided for field voltage and current, the SCR firing command percentage, and

IDP-1200

IDP-1200 Operation with ECS2100 and ECS/RW