9437200990 Rev C

Var

This screen (Figure 58) is available only on systems equipped with var control.

Control of reactive power is enabled and disabled by the VAR Control button. When this button is
pressed, Enable and Disable buttons will appear and enable the user to turn control of vars on and off.

Var balance is adjusted by pressing the VAR Adjuster button. When the button is pressed, Raise and
Lower buttons will appear and enable the user to raise and lower the level of reactive power.

The 70BC-CS Manual button can be used to raise or lower the balance or manual reference. When the
button is pressed, Raise and Lower buttons will appear and enable the user to raise and lower the voltage
while operating in Manual mode.

Similarly, the 90DV-CS Auto button can be used to raise or lower the voltage while operating in Auto
mode.

Generator and excitation system values are displayed and controls are provided for control of the ac
(41A) breaker.

Figure 58. Var Screen

Power Factor

This Power Factor screen is shown in Figure 59. This screen is only available on systems with PF control.

Control of power factor is enabled and disabled by the PF Control button. When this button is pressed,
Enable and Disable buttons will appear and enable the user to turn control of power factor on and off.

Power factor balance is adjusted by pressing the PF Adjuster button. When the button is pressed, Raise
and Lower buttons will appear and enable the user to raise and lower the power factor.

The 70BC-CS Manual button can be used to raise or lower the balance or manual reference. When the
button is pressed, Raise and Lower buttons will appear and enable the user to raise and lower the voltage
while operating in Manual mode.

Similarly, the 90DV-CS Auto button can be used to raise or lower the voltage while operating in Auto
mode.

Generator and excitation system values are displayed and controls are provided for control of the ac
(41A) breaker.

IDP-1200 Operation with DECS-2100 and DECS/RW

IDP-1200