This chapter provides the information needed for mounting the IDP-1200 and the Ethernet switch.

Mounting the IDP-1200

Information is provided for two types of IDP-1200 installations:

Retrofit installation in an ECS2100 enclosure that currently houses a PanelMate display

New installation in a panel separate from the control system enclosure

Mounting Considerations

The IDP-1200 is intended for mounting in a cutout on a vertical panel in an environment where the
ambient temperature falls between 0 and 50

°C (32 and 122°F). Observe the following considerations and

guidelines when preparing to mount the IDP-1200.

Location and Environmental Considerations

The IDP-1200 is intended for mounting in a vertical panel. If mounting the IDP-1200 in a slanted panel,
the panel should not deviate more than 30

° from vertical. If the panel slants more than 30°, you must

ensure that the ambient temperature surrounding the IDP-1200 does not exceed 40

° (104°F). This may

require the use of external cooling equipment (a fan or air conditioner). To enhance ventilation and
maintenance, the IDP-1200 should be installed at least 4 inches (102 millimeters) away from adjacent
equipment. Heat created by nearby equipment must not cause the ambient temperature surrounding the
IDP-1200 to exceed its maximum operating temperature.

Mounting Panel Thickness

The IDP-1200 can be mounted on a panel whose thickness is no less than 0.06 inches (1.6 millimeters)
and no more than 0.39 inches (10.0 millimeters).

Retrofit Installations

Two types of IDP-1200 installation kits are available for retrofit installation. Kit part number 9437200102 is
designed for replacement of a PanelMate display mounted in an ECS2100 system enclosure door hinged
on the left-hand side. Kit part number 9437200104 is designed for replacement of a PanelMate display
mounted in an ECS2100 system enclosure door hinged on the right-hand side. Each kit consists of the
following:

IDP-1200 display panel

Mounting bracket

Mounting bracket hinge assembly

Ethernet switch

Rubber grommet (kit P/N 9437200102 only)

Warning!

The excitation cubicle housing the display panel must be removed
from service and all related operating/control power voltage de-
energized before proceeding with the following procedures.



IDP-1200

Mounting