How to perform manual tests – Seaward Supernova XE User Manual

Page 41

Advertising
background image

How to perform Manual Tests

31

Appliance Test Results

It is possible to view the results obtained for a certain appliance by
highlighting the appliance number and pressing the ENTER button.

APPLIANCE :

A1212654673891

SITE
USER

: KITCHEN
: BOB

TESTCODE1 :

1027353823

TESTCODE 2

: 312169743A

TEST OUTPUT

LIMIT

RESULT

STATUS

EARTH BOND

25A

0.1ohms

0.99

PASS

EARTH BOND

25A

0.1ohms

0.98

PASS

INSULATION 500V 2Mohms

20.67 PASS

SUB LEAKAGE

7.5mA

<0.25

PASS

LOAD

2.00kVA

PASS

A fast key may illuminate to ‘view comments’

Use the Red button to return to the previous menu.

How to perform Manual Tests

Manual mode provides the user with direct access to the tests. In
this mode individual tests can be selected and performed. Appliance
numbers, sites, users and testcodes can still be assigned to
appliances if required, though this is not essential.

Entering Manual Mode

Use the fast key to select Manual Mode from the Main Menu.