Chapter 7 specifications – Seaward Supernova XE User Manual

Page 84

Advertising
background image

Earth Bond Test

74

Chapter 7 Specifications

Earth Bond Test

Test Voltage * .....................................................6V nominal (no load)

Test Current *.....................4A, 10A, 25A selectable (into s/c load)

Range .......................................................................... 40m

Ω - 19.99Ω

Resolution...............................................................................0.01

Accuracy................................................ +/- 5% of reading, +/- 2 digits

Pass

Levels...........................................................................selectable

Misc.............................................4-wire measurement, floating earth

DC Earth Bond Test

Test Voltage * .....................................................4V nominal (no load)

Test Current *.....................-200mA,+200mA selectable (into s/c
load)

Range .......................................................................... 40m

Ω - 19.99Ω

Resolution...............................................................................0.01

Accuracy................................................ +/- 5% of reading, +/- 2 digits

Pass

Levels...........................................................................selectable

Misc.............................................4-wire measurement, floating earth

Earth Screen Test

Test Voltage * ..............................................100mV nominal (no load)

Test Current *...............................................100mA (into s/c load)

Range............................................................................ 40m

Ω - 19.99Ω

Resolution...............................................................................0.01