Grounding, Power, Cooling – H3C Technologies H3C S10500 Series Switches User Manual

Page 12

Advertising
background image

4

EMI

Electromagnetic interference (EMI) might be coupled from the source to the switch through the following

coupling mechanisms:

Capacitive coupling

Inductive coupling

Radiative coupling

Common impedance coupling

Conductive coupling

To prevent EMI, take the following actions:

If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE) to
filter interference from the power grid.

Keep the switch far away from radio transmitting stations, radar stations, and high-frequency
devices to make sure the EMI levels do not exceed the compliant range.

Use electromagnetic shielding, for example, shielded interface cables, when necessary.

To prevent signal ports from getting damaged by over-voltage or over-current caused by lightning
strikes, only route interface cables indoors.

Grounding

Using a good grounding system to protect your switch against lightning shocks, interferences, and ESD

is essential to the operating reliability of your switch.
Make sure the resistance between the chassis and the ground is less than 1 ohm.

Power

Perform the following tasks to meet the power requirements:

1.

Calculate the system power consumption.
The system power consumption varies by card type and density. For more information about
system power consumption calculation, see "

Appendix A Chassis views and technical

specifications

."

2.

Select power modules and identity the number of power modules.
The total maximum output power of all power modules must be higher than the system power
consumption. For more information about available power modules, see "

Appendix B FRUs and

compatibility matrixes

."

3.

Verify that the power system at the installation site meets the requirements of the power modules,
including the input method and rated input voltage.

Cooling

Plan the installation site for adequate ventilation.

Leave at least 10 cm (3.94 in) of clearance at the inlet and outlet air vents.

The rack for the switch has a good cooling system.