12 securing the server, Securing the server – FUJITSU SPARC ENTERPRISE M5000 User Manual

Page 127

Advertising
background image

Chapter 6

Storage Devices Replacement

6-21

3. Connect the power and serial cables to the rear of the CD-RW/DVD-RW Drive

Backplane.

Caution –

Do not force the CD-RW/DVD-RW Drive Unit into a slot. Doing so can

cause damage to the drive and server.

4. Install the CD-RW/DVD-RW Drive Unit.

See

“Installing the CD-RW/DVD-RW Drive Unit” on page 6-16

.

6.2.12

Securing the Server

Caution –

The motherboard unit is heavy. Two people are recommended to lift the

unit.

1. Install the motherboard unit.

This step includes installing the motherboard cradle, securing the busbar screws,
and installing the CPU modules and filler panels See

“Installing the SPARC

Enterprise M5000 Motherboard Unit” on page 13-10

.

2. Install the top cover.

This step includes sliding the server in to the equipment rack and restoring the
antitilt features to their original position. See

“Replacing the Top Cover” on

page 5-8

.

3. Power the server on.

This step includes reconnecting power cables, verifying the state of the LEDs,
and turning the keyswitch to the Locked position. See

“Powering the Server On

Using Software” on page 4-13

.

Note –

If the Solaris automatic booting is set, use the sendbreak -d domain_id

command after the display console banner is displayed but before the system starts
booting the operating system to get the ok prompt.

4. Confirm the hardware.

This step includes running programs to be certain all components are mounted
again and then booting the operating system.

Refer to

“Verifying Hardware Operation” on page 4-9

for more information.