I/O Unit Replacement

The I/O units are cold replacement components.

8.3.1

Accessing the I/O Unit

Caution –

There is an electrical hazard if the power cords are not disconnected. All

power cords must be disconnected to completely remove power from the server.

Power off the server.

This step includes turning the key switch to the Service position, confirming that the
POWER LED is off, and disconnecting power cables. See

“Powering the Server Off

Using Software” on page 4-12

.

8.3.2

Removing the I/O Unit

Caution –

Use proper ESD grounding techniques when handling components. See

“Safety Precautions” on page 1-1

.

1. Disconnect and label all the cables that connect to the I/O unit.

2. Remove the cassettes from the I/O unit.

See

“Removing the PCI Cassette” on page 8-5

.

3. Disconnect the cabinet end of the cable management arm.