Appendix E

UPS Controller

E-3

ON:Indicates contacts are closed

OFF: Indicates contacts are open

Note1: Use a UPS capable of normal battery power supply operation for at least 10 to 60 seconds after this signal is turned on.

Note2: Use a UPS capable of normal battery power supply output without turning on the *ACOFF in an instantaneous commercial AC

power failure lasting two seconds or less.

E.4

Power Supply Conditions

TABLE E-2

and

TABLE E-3

list the electrical specifications for the UPS interface.

E.4.1

Input circuit

Limit the signal-line chatter period to 1ms or less.

*ACOFF

Signal indicates power failure at the commercial
AC supply connector to the UPS

9

Normal: OFF
Power failure: ON
(Note2)

SG

Signal ground

5

ER

Signal indicates the main unit is running
(Equipment Ready)

1

Do not connect to ER
signal pin.

TABLE E-2

Electrical specifications

Signal name

Input conditions

*BPS/*UALM

No voltage relay contact
Contact rating DC 12 V, 10 mA or more (maximum 0.5A)
Use of metallic contact, or lead relay is recommended.

*BTL

*ACOFF

Signal name

Definitions

Pin number

Remarks