10. LEAK TEST, EVACUATION AND

ADDITIONAL REFRIGERANT CHARGE

Perform an air-tightness test for this package A/C. Check

that there is no leakage from any of the connections.

Air and moisture in the refrigerant system may have

undesirable effects as indicated below.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the refrigerant circuit may freeze and block

capillary tubing

water may lead to corrosion of parts in the refrigerant

system

Therefore, the indoor unit and tubing between the indoor

and outdoor unit must be leak tested and evacuated to

remove any noncondensables and moisture from the

system.

Air Purging with a Vacuum Pump (for Test Run)

Preparation

Check that each tube (both liquid and gas tubes) between

the indoor and outdoor units has been properly connected

and all wiring for the test run has been completed. Remove

the valve caps from both the gas and liquid service valves

on the outdoor unit. Note that both liquid and gas tube

service valves on the outdoor unit are kept closed at this

stage.

The refrigerant charge at the time of shipment is only

guaranteed sufficient for a tubing length of up to 100 ft.

The tubing may exceed this length, up to the maximum

permitted length; however, an additional charge is

necessary for the amount that the tubing exceeds 100 ft.

(No additional refrigerating machine oil is needed.)

10-1. Leak Test

(1) With the service valves on the outdoor unit closed,

remove the 1/4 in. flare nut and its bonnet on the gas

tube service valve. (Save for reuse.)

(2) Attach a manifold valve (with pressure gauges) and dry

nitrogen gas cylinder to this service port with charge

hoses.

Manifold gauge

CAUTION

Use a manifold valve for air

purging. If it is not available,

use a stop valve for this

purpose. The “Hi” knob of the

manifold valve must always be

kept closed.