5-3. Wiring System Diagrams

Basic wiring diagram for standard control

U2

U1

L1

L2

U1

U2

1

2

G

2

1

WHT

Remote
controller

D

A

Indoor

unit

B

L1
L2

Grounding line

BLK

2

1

Inter-unit power line

208 / 230 V, 60 Hz

Power supply
208 / 230 V, 60Hz

Grounding line

C

Ground

Outdoor unit

INV unit

1

2

G

(1) Refer to Section 5-2. Recommended Wire Length

and Wire Diameter for Power Supply System for

the explanation of “A”, “B”, “C”, “D”, and “E”, in the

above diagrams.

(2) Inter-Unit Control Wiring (C) and remote control-

ler wiring (D), (E) have no polarity. But for other

wiring, respect polarity. Be sure to connect as

shown in the Wiring System Diagram.

(3) In case of separate supply connection to indoor

unit, over current protection must be provided

between power source and indoor unit.

NOTE

1

2 G

Inter-unit

power wiring

U1

Inter-unit

control wiring

U2

5P terminal board

X, T, U Type

Remote

controller wiring

Inter-unit

control wiring

4P terminal board

1

2 G

Inter-unit

power wiring

U1 U2

K Type

Remote

controller wiring

Indoor Unit

Control Wiring

Type

(B) Power Supply

AWG #14

(C) Inter-Unit Control Wiring

(D) Remote Control Wiring

(E) Control Wiring For Group Control

Trade Size

of Conduit

MOP

(Fuse or HACR

type circuit breaker)

AWG #18

Use high voltage wire (300 V)

*1

AWG #18

*2

(0.75 mm

2

)

Max. 1,650 ft.

Max. 3,300 ft.

Max. 1,650

ft. (Total)

AWG #18

*2

(0.75 mm

2

)

3/4 in.

15 A

Max. length 67 ft.

X, K, T, U

*1

With ring-type wire terminal.

*2

Wire joint connection.

Inter-unit

power wiring

Power wiring

Inter-unit

control wiring

8P terminal board

CH Type

U1 U2 1 2 G L1 L2

MAXIMUM OVER CURRENT PROTECTION 15 A
(FUSE OR HACRTYPE CIRCUIT BREAKER)