7-15. Misoperation Alarm Indicators

A blinking lamp for other than the signal receiving unit

filter shows that a problem has occurred in the unit, so

make an inspection. (Refer to servicing information in

the service manual, etc.) Also, if wired remote control-

ler and dedicated service check lines (854-9-9536-

044-97: service use) are available, then detailed error

information can be obtained by connecting to the

service connector as shown in the drawing. For

information on how to connect to the signal receiving

unit, refer to the instruction manual that came with the

dedicated service check lines.

Fig. 7-23

ALL•
RCU : SUB

RCU : MAIN
NORMAL

PCB CHK.
TEST RUN

Service
connector

Lamp

OPERATION

TIMER

STANDBY

Bright

Cause of Trouble

lamp

lamp

lamp

No power supply or mis-wiring of signal receiving unit.

S.C.* errors between the indoor unit’s controller (PCB) and

signal receiving unit.

S.C. errors between indoor and outdoor units.

Alternately

Indoor unit protector is activated.

Alternately

Outdoor unit protector is activated.

Compressor protector is activated.

Concurrent

Mis-setting of indoor unit.

Concurrent

Mis-setting of outdoor unit.

Table 7-2

*

S.C.: Serial communications

OPERATION lamp

TIMER lamp

STANDBY lamp

FILTER lamp

Fig. 7-24