3-2. Use R410A exclusive cylinder only.

When charging with a refrigerant cylinder, use an
electronic scale for charging refrigerant. In this
case, if the volume of refrigerant in the cylinder
becomes less than 20% of the fully-charged
amount, the composition of the refrigerant starts
to change. Thus, do not use the refrigerant if the
amount in the charging cylinder is less than 20%.

Also, charge the minimum necessary amount to
the charging cylinder before using it to charge the
air conditioning unit.

Valve

Single valve
Charge liquid refrigerant with
cylinder in up-side-down position.

Single valve (with siphon tube)
Charge with cylinder in normal position.

Liquid

Valve

Liquid

Configuration and characteristics of cylinders

Fig. 1