7-23. When Setting Indoor Unit Control PCB Switch for Wall-Mounted Indoor Unit

When using either the wired or wireless remote controller, refer to the tables below and accordingly slide the switch on

the indoor unit control PCB.

If this setting is not made correctly an alarm will occur. (The operation lamp on the display blinks.)

This setting is not necessary if both the wired remote controller

and wireless remote controller are used.

However, when you use indoor unit KHS type, set the wired

remote controller address connector on the PCB from main to

sub position.

The slide switch setting at the time of factory shipment for

model KH type is “A”, and for model KHS type is “B.”

KH(S)3072 / 3672R, KHH(S)2672R

A

Nos. 1, 2 OFF, No. 3 ON

B

Nos. 1, 2, 3 all OFF

When using

wireless

remote

controller

When using

wrired

remote

controller

A

Nos. 1, 2 OFF, No. 3 ON.

B

Nos. 1, 2, 3 all OFF

When using

wireless

remote

controller

When using

wired

remote

controller

KH(S)2672R

Wired remote controller

address connector

RCU. ADR

Main

Sub

RCU check

Remote controller