background image

2-2. Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 2-1)

damp, humid or uneven locations

DO:

choose a place as cool as possible.

choose a place that is well ventilated and outside
air temperature does not exceed maximum 115°F
constantly.

allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-2)

use lug bolts or equal to bolt down unit, reducing
vibration and noise.

if cooling operation is to be used when the outdoor
air temperature is 23°F or below, install a duct on
the outdoor unit.

Installation space

Distance between obstructions and the unit air inlet

and outlet must be as shown below.

Fig. 2-1

Fig. 2-3

Fig. 2-4

Out-
door
unit

Heat source

Hot air

Exhaust fan

Anchor bolts
(4 pieces)

Installation requirements

provide a solid base (concrete block, 4"

× 16"

beams or equal), a minimum of 6" above ground
level to reduce humidity and protect the unit against
possible water damage and decreased service life.
(Fig. 2-4)

use lug bolts or equal to bolt down unit, reducing
vibration and noise.

*4

*2

*3

*1

More than 25/64"

More than
3.3 ft.

More than 25/64"

Inlet side C

Outlet side

CAUTION

Concerning inlet-side distance “C” (Fig. 2-2)
The minimum for distance “C” is 6" if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 8".

If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.

If wall *1 is on the outlet side (Fig. 2-2), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 2-2), then the minimum distance for “A” and “B” is 80" (Fig. 2-3). Even
if there is no wall on the outlet side, a minimum of 3.3 ft. is required.

Fig. 2-2

*1

Inlet side
More than 8"

(field supply)

A

B

(Ground)

Air direction chamber

(Obstruction above unit)

(Obstruction on
inlet side)

17

07-115 SSHP_II 5/7/07 3:59 PM Page 17