8-2. Electrical Wiring

B1

Indoor unit PCB

CRV
(CN91: WHT)

2P terminal base

Indoor unit

System controller

Accessary connector

Wire joint connection

B2

B3

B4

B5

B6

U1

U2

How to connect electrical wiring

(1)

Connect B1, B2 to indoor PCB CRV connector
using accessary 2P connector. (*No polarity)
Total wire length is less than 985 ft. and size is
AWG#18.

(2)

Connect B5, B6 to indoor unit 2P terminal base.
(*No polarity). Wire size is AWG#18.

Basic wiring

B1:

B2:

B3:

Not be used

B4:

Auxiliary of inter-unit control wiring

B5:

B6:

Terminals for remote monitoring

A1:

Input for turning on air conditioners concurrently.

A2:

Input for turning off air conditioners concurrently.

A3:

Common input for turning air conditioners on or off.

A4:

ON operation state indicator output.

A5:

Alarm indicator output.

A6:

Common indicator output.

Basic wiring diagram of control wiring

A max. of 64 indoor units and 30 outdoor units
can be connected in 1 system.

Up to 10 system controllers can be connected
in 1 system.

Fig. 8-3

Power supply: DC12V *No polarity
To CRV connector (CN91) on indoor PCB

Inter-unit control wiring. (Low voltage)
To indoor unit 2P terminal base (U1, U2)
*No polarity

Inter-unit
control wiring

System controller

RC1

1-1

RC2

RC3

2-1

3-1

Fig. 8-4

A1

<Back side of system controller>

A2

A3

A4

A5

A6

B6

B5

B4

B3

B2

B1