10-3. Charging Additional Refrigerant

Charging additional refrigerant (calculated from the

liquid tube length as shown on page 14, Amount of

additional refrigerant charge) using the liquid tube

service valve. (Fig. 10-5)

Use a balance to measure the refrigerant accurately.

If the additional refrigerant charge amount cannot

be charged at once, charge the remaining

refrigerant in liquid form by using the gas tube

service valve with the system in Cooling mode at

the time of test run. (Fig. 10-6)

* If an additional refrigerant charge has been

performed, list the refrigerant tubing length and

amount of additional refrigerant charge on the

product label (inside the panel).

10-4. Finishing the Job

(1) With a hex wrench, turn the liquid tube service

valve stem counter-clockwise to fully open the

valve.

(2) Turn the gas tube service valve stem counter-

clockwise to fully open the valve.

(3) Loosen the charge hose connected to the gas

tube service port (5/16 in.) slightly to release the

pressure, then remove the hose.

(4) Replace the 5/16 in. flare nut and its bonnet on the

gas tube service port and fasten the flare nut

securely with an adjustable wrench or box wrench.

This process is very important to prevent gas from

leaking from the system.

(5) Replace the valve caps at both gas and liquid

service valves and fasten them securely.

CAUTION

To avoid gas from leaking

when removing the charge

hose, make sure the stem

of the gas tube is turned all

the way out (“BACK SEAT”

position.

Valve

Liquid

Manifold valve

Pressure
gauge

Lo

Hi

Outdoor unit

Liquid
tube

Gas
tube

Close

Close

Close

R410A

Outdoor unit

Liquid
tube

Gas
tube

Open

Open

Open

103