3-4. Installing the Drain Piping

(1) Prepare standard hard PVC pipe for the drain and

use the supplied drain hose and hose band to pre-

vent water leaks.

The PVC pipe must be purchased separately. The

transparent part allows you to check drainage.

(Fig. 3-6)

(2) After checking the drainage, wrap the supplied

packing and drain pipe insulator around the pipe.

(Fig. 3-7)

Ensure the drain pipe has a downward gradient (1/100

or more) and that there are no water traps.

NOTE

CAUTION

Tighten the hose clamps so

their locking nuts face upward.

(Fig. 3-6)

CAUTION

Do not install an air bleeder tube, as this may cause

water to spray from the drain tube outlet. (Fig. 3-8)

If it is necessary to increase the height of the drain

pipe, the section directly after the connection port

can be raised a maximum of 19-11/16 in. Do not

raise it any higher than 19-11/16 in., as this could

result in water leaks. (Fig. 3-9)

Do not install the pipe with an upward gradient from

the connection port. This will cause drain water to

flow backwards and leak when the unit is stopped.

(Fig. 3-10)

Do not apply force to the piping on the unit side

when connecting the drain pipe. The pipe should

not be allowed to hang unsupported from its

connection to the unit. Fasten the pipe to a wall,

frame, or other support as close to the unit as

possible. (Fig. 3-11)

Provide insulation for any drain pipe that is run

indoors.

Drain hose
(supplied)

Packing
(supplied)

Transparent part for
checking drainage

Hose band
(supplied)

Drain hose
adapter
(supplied)

Hard PVC pipe
(not supplied)

Fig. 3-6

Drain insulator (supplied)

Fig. 3-7

Air bleeder

Fig. 3-8

11-3/4 in. or less (as short as possible)

19-11/16 in. or less

Fig. 3-9

Upward gradient

Fig. 3-10

Support
pieces

Fig. 3-11