5. ELECTRICAL WIRING

5-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit

as shown on its nameplate, then carry out the

wiring closely following the wiring diagram.

(2) Provide a power outlet to be used exclusively for

each unit, and a power supply disconnect and

circuit breaker for overcurrent protection should be

provided in the exclusive line.

(3) To prevent possible hazards from insulation

failure, the unit must be grounded.

(4) Each wiring connection must be done in

accordance with the wiring system diagram.

Wrong wiring may cause the unit to misoperate or

become damaged.

(5) Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be

very dangerous. The manufacturer will accept no

responsibility for any damage or misoperation that

occurs as a result of such unauthorized changes.

(7) Regulations on wire diameters differ from locality

to locality. For field wiring rules, must follow your

LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8) To prevent malfunction of the air conditioner

caused by electrical noise, care must be taken

when wiring as follows:

The remote control wiring and the inter-unit

control wiring should be wired apart from the

inter-unit power wiring.

Use shielded wires for inter-unit control wiring

between units and ground the shield on both

sides.

(9) If the power supply cord of this appliance is dam-

aged, it must be replaced by a repair shop

appointed by the manufacturer, because special-

purpose tools are required.

(10) All wiring used must be Class 1.

5-2. Recommended Wire Length and Wire Diameter for Power Supply System

You must follow LOCAL ELECTRICAL CODES for wiring.

Outdoor Unit

Model Name (A) Power Supply

Trade Size

of Conduit

3/4 in.

3/4 in.

3/4 in.

Trade Size

of Conduit

1-1/4 in.

1-1/4 in.

1-1/4 in.

Power Supply Terminal Base

* AWG = American Wire Gauge

50 A

50 A

50 A

Capacity Max. Wire Diameter

AWG #6

AWG #6

AWG #6

MOP

(Fuse or HACR

type circuit breaker)

30 A

35 A (230/208 V)

35 A (230/208 V)

AWG #12

Max. length 64 ft.

AWG #10

Max. length 92 ft.

AWG #10

Max. length 92 ft.

CH2672R

CH3072R

CH3672R

3/4 in.

1-1/4 in.

50 A

AWG #6

40 A

AWG #10

Max. length 81 ft.

CH4272R

Model Name (A) Power Supply

Trade Size

of Conduit

3/4 in.

3/4 in.

3/4 in.

Trade Size

of Conduit

1-1/4 in.

1-1/4 in.

1-1/4 in.

Power Supply Terminal Base

50 A

50 A

50 A

Capacity Max. Wire Diameter

AWG #6

AWG #6

AWG #6

MOP

(Fuse or HACR

type circuit breaker)

25 A

30 A (230/208 V)

30 A (230/208 V)

AWG #12

Max. length 76 ft.

AWG #10

Max. length 99 ft.

AWG #10

Max. length 99 ft.

C2672R

C3072R

C3672R

3/4 in.

1-1/4 in.

50 A

AWG #6

35 A

AWG #10

Max. length 81 ft.

C4272R