U

3-23. Suspending the Indoor Unit

Depending on the ceiling type:

• Insert suspension bolts as shown in Fig. 3-93

or

• Use existing ceiling supports or construct a suitable

support as shown in Fig. 3-94.

(1) When placing the unit inside the ceiling,

determine the pitch of the suspension bolts

referring to the dimensional data on the previous

page. (Fig. 3-92)

Tubing must be laid and connected inside the

ceiling when suspending the unit. If the ceiling is

already constructed, lay the tubing into position for

connection to the unit before placing the unit inside

the ceiling.

(2) Screw in the suspension bolts allowing them to

protrude from the ceiling as shown in Fig. 3-93.

(Cut the ceiling material, if necessary.)

(3) Thread the 2 hexagonal nuts and washers (field

supply) onto the 4 suspension bolts as shown in

Figs. 3-95 and 3-96. Use 2 sets of nuts and wash-

ers (upper and lower), so that the unit will not fall

off the suspension lugs.

WARNING

It is important that you use

extreme care in supporting the

indoor unit inside the ceiling.

Ensure that the ceiling is strong

enough to support the weight of

the unit. Before hanging the unit,

test the strength of each

attached suspension bolt.

Hole-in-anchor
Hole-in-plug

Concrete

Insert

Suspension bolt (M10 or 3/8")
(field supply)

Fig. 3-93

Ceiling tiles

Ceiling support

Fig. 3-94

Nuts and washers

(2 sets)

Suspension bolt

Suspension lug

Upper

Lower

Fig. 3-95

Suspension bolt

Hexagonal nut

Fig. 3-96