SC

(a)

Zone registration using the remote controller

(RCS-SH80UG)

(Determination of central address)

In this case, after confirming which indoor unit is

connected to the remote controller and that the air

conditioner in the OFF state, you set the central

addresses one at a time.

If the system has no remote controller, connect a

remote controller to the system temporarily. Then

follow this procedure.

The indoor unit address must already have been set

before performing zone registration. If necessary, refer

to the Installation Manual supplied with the outdoor

unit.

(1)

Press the

and

buttons on the remote

controller at the same time for more than

(2)

Do not press

buttton.

(3)

Once in this mode, the UNIT No., CODE No., No.

of SET DATA and

indications will flash on

the display as shown Fig. 8-6.

In case of group control “ALL” instead of “UNIT No.”

will flash on the display. Select the main indoor unit

address by pressing the

button once.

(4)

Set CODE No. to 03 using the

and

(

) buttons.

CODE No. 03 must be selected to perform zone

registration using the remote controller.

(5)

Set the Central address you want to assign

to the indoor unit address using the

and

(

) buttons according to the zone

registration table.

(6)

Press the

button. The CODE No. and Central

address changes from flashing to ON state. If you

make a mistake, press the

button and

reset the central address.

(7)

Press the

button to finish zone registration.

Fig. 8-6

For example, in this case

Indoor unit address: 1–8
Central address

: 17 (Zone 2, Group 1)

Fig. 8-7

NOTE

NOTE

NOTE