Sanyo C4272R S/C User Manual

Page 102

Advertising
background image

C

102

Fig. 10-4

(3) Pressurize the system up to 4.15 MPa

(42 kgf/cm

2

G) with dry nitrogen gas and close the

cylinder valve when the gauge reading reaches

4.15 MPa (42 kgf/cm

2

G). Then, test for leaks with

liquid soap.

(4) Do a leak test of all joints of the tubing (both

indoor and outdoor) and both gas and liquid

service valves. Bubbles indicate a leak. Wipe

off the soap with a clean cloth after the leak test.

(5) After the system is found to be free of leaks,

relieve the nitrogen pressure by loosening the

charge hose connector at the nitrogen cylinder.

When the system pressure is reduced to normal,

disconnect the hose from the cylinder.

10-2. Evacuation

Be sure to use a vacuum pump that includes a

function for prevention of back-flow, in order to

prevent back-flow of pump oil into the unit tubing

when the pump is stopped.

Perform vacuuming of the indoor unit and tubing.

Connect the vacuum pump to the gas tube valve

and apply vacuum at a pressure of –755 mmHg

(5 Torr) or below.

Continue vacuum application for a minimum of 1

hour after the pressure reaches –755 mmHg.)

(1) Attach the charge hose end described in the

preceding steps to the vacuum pump to evacuate

the tubing and indoor unit. Confirm that the “Lo”

knob of the manifold valve is open. Then, run the

vacuum pump.

(2) When the desired vacuum is reached, close the

“Lo” knob of the manifold valve and turn off the

vacuum pump. Confirm that the gauge pressure is

under 667 Pa (–755 mmHg, 5 Torr) after 4 to 5

minutes of vacuum pump operation.

Manifold valve

Pressure
gauge

Lo

Hi

Vacuum pump

Outdoor unit

Liquid
tube

Gas
tube

Close

Close

Open

CAUTION

To avoid nitrogen entering the

refrigerant system in a liquid

state, the top of the cylinder

must be higher than the bottom

when you pressurize the

system. Usually, the cylinder is

used in a vertical standing

position.

CAUTION

Use a cylinder specifically

designed for use with R410A.

07-115 SSHP_II 5/7/07 4:00 PM Page 102