Sanyo C4272R S/C User Manual

Page 13

Advertising
background image

13

1-5. Tubing Size

Single type

Refrigerant tubing between the indoor and outdoor units
should be kept as short as possible.

The length of the refrigerant tubes between the indoor
and outdoor units are limited by the elevation difference
between the 2 units. During tubing work, try to make both
the tubing length (L) and the difference in elevation (H1)
as short as possible. Refer to Table 1-10.

Table 1-9

Single

Main tubing L

H1

H1

H1

< 100

< 50

Maximum indoor-outdoor
height difference

If outdoor unit is higher

If outdoor unit is lower

Indoor unit type

26, 30, 36 types

42 type

Maximum length

165 ft.

165 ft.

Charge-less tubing length (actual length)

10 – 100 ft.

15 – 100 ft.

Additional charge per 1 ft.

0.43 oz.

07-115 SSHP_II 5/7/07 3:59 PM Page 13

Advertising