11. TEST RUN

11-1. Preparing for Test Run

Before attempting to start the air conditioner,
check the following:

(1) All loose matter is removed from the cabinet

especially steel filings, bits of wire, and clips.

(2) The control wiring is correctly connected and all

electrical connections are tight.

(3) The protective spacers for the compressor used for

transportation have been removed. If not, remove

them now.

(4) The transportation pads for the indoor fan have

been removed. If not, remove them now.

(5) The power has been supplied to the unit for at least

5 hours before starting the compressor. The bottom

of the compressor should be warm to the touch and

the crankcase heater around the feet of the

compressor should be hot to the touch. (Fig. 11-1)

(6) Both the gas and liquid tube service valves are

open. If not, open them now. (Fig. 11-2)

(7) Request that the customer be present for the trial

run.

Explain the contents of the instruction manual, then

have the customer actually operate the system.

(8) Be sure to give the instruction manual and warranty

certificate to the customer.

(9) When replacing the control PCB, be sure to make

all the same settings on the new PCB as were in

use before replacement.

The existing EEPROM is not changed, and is

connected to the new control PCB.

Fig. 11-1

Fig. 11-2

Power mains switch

(Power must be turned ON
at least 5 hours before
attempting test run)

ON

Liquid tube

Gas tube