Sanyo C4272R S/C User Manual

Page 99

Advertising
background image

99

Fig. 9-10

Fig. 9-9

Fig. 9-8

Fig. 9-11

Do not use a spanner to tighten the valve stem caps.
Doing so may damage the valves.

Depending on the installation conditions, applying
excessive torque may cause the nuts to crack.

Precautions for Packed Valve Operation

If the packed valve is left for a long time with the valve
stem cap removed, refrigerant will leak from the valve.
Therefore, do not leave the valve stem cap removed.

Use a torque wrench to securely tighten the valve stem
cap.

Valve stem cap tightening torque:

9-3. Insulating the Refrigerant Tubing

Tubing Insulation

Thermal insulation must be applied to all unit tubing,
including the distribution joint (purchased separately).

* For gas tubing, the insulation material must be heat

resistant to 248°F or above. For other tubing, it must be
heat resistant to 176°F or above.

Insulation material thickness must be 13/32 in. or greater.

If the conditions inside the ceiling exceed DB 86°F and
RH 70%, increase the thickness of the gas tubing
insulation material by 1 step.

Taping the flare nuts

Wind the white insulation tape around the flare nuts at the
gas tube connections. Then cover up the tubing
connections with the flare insulator, and fill the gap at the
union with the supplied black insulation tape. Finally, fasten
the insulator at both ends with the supplied vinyl clamps.
(Fig. 9-10)

Insulation material

The material used for insulation must have good insulation
characteristics, be easy to use, be age resistant, and must
not easily absorb moisture.

CAUTION

CAUTION

Never grasp the drain or refrigerant connecting
outlets when moving the unit.

Unit side
insulator

Insulation tape (white)

(supplied)

Sealer (supplied)

Flare insulator (supplied)

Tube insulator
(not supplied)
Heat resistant
248ºF or above

Vinyl clamps (supplied)

Flare nut

The procedure used for
installing the insulator for
both gas and liquid
tubes is the same.

Seal

Flare
insulator

Vinyl
clamp

Insulation
tape

Refrigerant tubing and insulator
(not supplied)

Drain pipe and insulator
(not supplied)

Drain insulator
and clamp.
Large
(supplied)

Packing
clamp.
Small
hose band
(supplied)

2 tubes arranged together

If the exterior of the outdoor unit
valves has been finished with a
square duct covering, make sure
you allow sufficient space to
access the valves and to allow
the panels to be attached and
removed.

Charging port

8 – 10 N • m (80 – 100 kgf • cm)

ø3/8

"

(Liquid side)

19 – 21 N • m (190 – 210 kgf • cm)

ø5/8

"

(Gas side)

28 – 32 N • m (280 – 320 kgf • cm)

Inter-unit
control wiring

Gas tube

Liquid tube

Armoring tape

Insulation

Charging port

Valve stem cap

Valve stem

Main valve

Packed valve

After a tube has been insulated,
never try to bend it into a nar-
row curve because it can cause
the tube to break or crack.

07-115 SSHP_II 5/7/07 4:00 PM Page 99

Advertising
This manual is related to the following products: