U

Fig. 3-97 shows an example of installation.

3-24. Installing the Drain Piping

(1) Prepare standard hard PVC pipe for the drain and

use the supplied hose band to prevent water leaks.

The PVC pipe must be purchased separately.

When doing this, leave a gap between the drain

socket of the unit and the PVC pipe to allow the

drainage to be checked. The transparent drain

pipe allows you to check drainage. (Fig. 3-98)

(2) After connecting the drain piping securely, wrap the

supplied packing and drain pipe insulator around

the pipe, then secure it with the supplied clamps.

(Fig. 3-99)

Make sure the drain pipe has a downward gradient

(1/100 or more) and that there are no water traps.

NOTE

CAUTION

Tighten the hose clamps so

their locking nuts face upward.

(Fig. 3-98)

Air outlet duct

Air-outlet grille

Ceiling material

Indoor unit

Bolt anchor

Suspension bolt

Air-intake duct

Air-intake grille

Drain hose
(supplied)

Packing
(supplied)

Transparent part for
checking drainage

Hose band
(supplied)

Drain hose
adapter
(supplied)

Hard PVC pipe
(not supplied)

Fig. 3-98

Drain insulator (supplied)

Clamps (supplied)

Fig. 3-99

Fig. 3-97