Chapter 2

Analog Input

© National Instruments Corporation

2-23

E Series User Manual

Therefore, half as many DIFF channel pairs are available compared to
individual channels.

Use DIFF input connections for any channel that meets any of the following
conditions:

The input signal is low-level (less than 1 V).

The leads connecting the signal to the device are greater than 3 m
(10 ft.).

The input signal requires a separate ground-reference point or return
signal.

The signal leads travel through noisy environments.

DIFF signal connections reduce noise pickup and increase common-mode
noise rejection. DIFF signal connections also allow input signals to float
within the common-mode limits of the PGIA.

Differential Connections for Ground-Referenced Signal Sources

Figure 2-9 shows how to connect a ground-referenced signal source to a
channel on the device configured in DIFF mode.

Figure 2-9. Differential Connections for Ground-Referenced Signal Sources

E Series Device Configured in DIFF Mode

PGIA

+

+

+

+

Vcm

Vs

Ground-

Referenced

Signal

Source

Common-

Mode

Noise and

Ground

Potential

AI GND

AI SENSE

Input Multiplexers

Vm

Measured

Voltage

Instrumentation

Amplifier

AI +

AI –

I/O Connector