Figure 3-3. ocu local loopback (dte option) – Zhone Technologies 900 User Manual

Page 96

Advertising
background image

3-8

IMACS System Release 5.1.6

Data Cards

Model No.

Running Head

OCU-DP Card User Screens and Settings

OCU-DP Card

LB

The OCU-DP card supports three Loopback options that test on the card itself. The dte option
loops the 4-wire analog interface of the OCU-DP port towards the attached CSU/DSU. It is
used to test the local cabling and the analog drivers in the OCU-DP card (see Figure 3-3).

The net-a (Network A) option loops the 4-wire OCU-DP interface towards the network. Use
it to test all of the OCU-DP card circuitry, the system common equipment, the WAN link card,
the remote equipment and the WAN line between the two sites (see Figure 3-4).

Note:

There are various types of test sets that can be used to generate loopbacks in the field.
When a test set is initiated for an OCU-DP card an “l” status should be present on
the port of the OCU-DP to indicate a loopback. If not, simply perform a “refresh”
operation to update the screen.

The net-d (Network D) option puts a loopback towards the network at the point where the
OCU-DP card interfaces with the system bus. It separates the OCU-DP card circuitry from the
system common equipment, WAN card, remote equipment, and WAN line between the two
sites (see Figure 3-5).

Figure 3-3. OCU Local Loopback (dte option)

OCU-DP Card

OCU-DP Card

CSU/DSU

CSU/DSU

Local

DTE

Remote

DTE

Carrier's DDS

Network

Local System

Local Site

Remote Site

Remote System