Configuring billing/tariff registers – E-Mon E-PS-S-HV-RTU User Manual

Page 105

Advertising
background image

Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Billing/TOU

PowerSmart Socket Power Quality Meter

105

Configuring Billing/Tariff Registers

To configure the meter billing/TOU registers, select
Energy/TOU from the Meter Setup menu.

The available options are shown in the following table:

Parameter

Options

Default

Description

Billing/TOU Registers

TOU

Unchecked

Checked

Unchecked

Links multi-tariff registers to the selected
energy source

Use Profile

Unchecked

Checked

Checked

Enables recording energy registers in
monthly/daily billing profile files (both total
and tariff registers if TOU is enabled).
Always enabled for all configured billing
registers.

Dmd Profile Unchecked

Checked

Unchecked

Enables recording maximum demand
registers in monthly/daily billing profile files
(both total and tariff registers if TOU is
enabled)

Sum Profile Unchecked

Checked

Checked

Enables recording total (summary) registers
in monthly/daily billing profile files. Always
enabled for all configured billing registers.

Units

None
kWh+ (delivered)
kWh- (received)
kvarh+ (delivered)
kvarh- (received)
kvarh Q1
kvarh Q2
kvarh Q3
kvarh Q4
kVAh (total)
kVAh+ (delivered)
kVAh- (received)

None

The register measurement unit and
quadrants.

Selected automatically for registers linked
to internal energy sources.

Select an appropriate measurement unit for
external pulse sources.