Chapter 5 Configuring the PowerSmart Socket PQM
General Meter Setup
94
PowerSmart Socket Power Quality Meter
Configuring Analog Outputs
The PowerSmart Socket PQM can provide one AO expansion
module with a total of 4 analog outputs with options for 0-1
mA, ±1mA, 0-20 mA and 4-20 mA.
To configure the analog outputs, select General Setup from
the Meter Setup menu, and then click on the Analog Outputs
tab. The setup entries will be blanked if the AO expansion
module is not installed in the meter.
The available analog output options are described in the
following table.
Option
Range
Description
AO type
0-1mA
±1mA
0-20mA
4-20mA
The analog output type. When connected to the
meter, shows the actual AO type received from
the device. When working off-line, select the
analog output option corresponding to your
analog module.
Output parameter
See Appendix C
Selects the measured parameter to be
transmitted through the analog output channel.
Zero scale
Defines the low engineering scale (in primary
units) for the analog output corresponding to a
lowest (zero) output current (0 or 4 mA)
Full scale
Defines the high engineering scale (in primary
units) for the analog output corresponding to a
highest output current (1 or 20 mA)
When you select an output parameter for the analog output
channel, the default engineering scales are set automatically.
They correspond to the maximum available scales. If the