Configuring the event recorder – E-Mon E-PS-S-HV-RTU User Manual

Page 111

Advertising
background image

Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Recorders

PowerSmart Socket Power Quality Meter

111

File

Record Size, Bytes

File Size, Bytes

Waveform Log

1068 × Number of Channels

Record size x Number of series
(events) × Number of records per
series

EN50160 Power Quality Log

32

Record size × Number of records

Fault Log

40

Record size × Number of records

The meter memory is pre-configured at the factory for
common data trending, billing, power quality and fault
recording applications as shown in the following table.

No.

File

Size,

Bytes

Channels

Number

of

Records

Number

of Events

Factory-set Configuration

1

Event log

21504

1000

1000

2

Data log #1

439296

5760

5760

Instrumentation 15-min data
trending for 60 days

3

Data log #2

439296

5760

5760

Instrumentation 15-min data
trending for 60 days

10

Data log #9

102400

12

56

56

EN50160 compliance statistics

11

Data log #10

38912

3

56

56

EN50160 harmonics survey

13

Data log #12

600064

11520

11520

15-min energy load profile for
120 days

14

Data log #13

208896

4320

4320

Fast fault RMS trend

15

Data log #14

191488

4320

4320

Fast PQ RMS trend

16

Data log #15

61440

20

24

24

Monthly Billing/TOU profile for
24 months

17

Data log #16

116736

20

120

120

Daily Billing/TOU profile for 120
days

18

Waveform log #1

3083264

6

480

120

PQ and fault waveforms:
32 samples/cycle × 64 cycles

19

Waveform log #2

776192

6

120

60

PQ waveforms:
128 samples/cycle × 64 cycles

20

Waveform log #3

518144

4

120

60

Fast transient waveforms:
1024 samples/cycle × 1 cycle

27

EN50160 Power
Quality log

33792

1000

1000

28

Fault log

41984

1000

1000

NOTE

The meter automatically performs de-fragmentation of the
memory each time you re-organize your files. This prevents
possible leakage of memory caused by fragmentation.
Depending on the data stored in the memory, it may take
from seconds to a couple of minutes.

Configuring the Event Recorder

To configure the Event log file:

1. Double click on the Event Log file partition with the left

mouse button.

Advertising
This manual is related to the following products: