Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Recorders

110

PowerSmart Socket Power Quality Meter

Option

Range

Description

Parameters

0-16

The number of parameters in a single data record

The device memory can be partitioned for a total of 22 log
files:

Event log

16 Data logs

3 Waveform logs

EN50160 PQ event log

Fault event log

Memory is allocated for each file statically when you set up
your files and will not change unless you re-organize the files.

To change the file properties or to create a new file:

1. Double click on the file you want to change.

2. Select desired parameters for your log.

3. Click OK.

For your reference, the record size and the number of records
available for your file are reported in the dialog box.

To delete an existing file partition:

1. Click on Delete.

2. Click OK.

For more information on configuring specific files, see the
following sections in this Chapter.

The following table can help you calculate an estimated file
size for conventional log files when planning your memory
allocation. The actual file size will normally be a bit bigger.

File

Record Size, Bytes

File Size, Bytes

Event Log

20

Record size × Number of records

Conventional Data Log

12 + 4 × Number of parameters

Record size × Number of records

EN50160 Compliance Statistics,
Data log #9

148 × 12 channels

Record size × Number of records

EN50160 Harmonics Survey,

Data log #10

220 × 3 channels

Record size × Number of records