Chapter 5 Configuring the PowerSmart Socket PQM

General Meter Setup

76

PowerSmart Socket Power Quality Meter

The following table lists available device options.

Display

Label

Parameter

Options

Default

Description

Power/Energy Options

Power Mode

Power Calculation
Mode

S=f(P, Q) (reactive
power mode),

Q=f(S, P) (non-
active power
mode)

S=f(P, Q)

The method used for calculating
reactive and apparent powers (see
“Power Calculation Modes” below)

Energy Roll

Energy Roll Value,
kWh

1000.0
10000.0
100000.0
1000000.0
10000000.0
100000000.0

100000000.0 The value at which energy

counters roll over to zero

End of Bill

End of Billing
Period

Auto (monthly)
Auto/COM
Auto/COM/Manual
COM
Manual

Auto
(monthly)

Triggering an end of billing period:

Auto – monthly self-reading

COM – remote via communications

Manual – from the front display

Tariff Control

Tariff Control

Calendar

Communication

Tariff inputs
D1…D10

1

Defines the tariff switching method
(see “Tariff Control” below).

Num Tariffs

Number of tariffs

1-8

1

Defines the number of season tariff
rates when no TOU calendar
schedule is available

Transf.
Correction

OFF (disabled)

ON (enabled)

OFF

Enables instrument transformer
correction – only via the front
display

Loss
Compensation

OFF (disabled)

ON (enabled)

OFF

Enables transformer/line loss
compensation – only via the front
display

Demand Forgiveness (Cold Load Pickup)

Dmd. Delay

Demand Delay,
min

0-60 min

0=disabled

0

The forgiveness time after an
outage that the meter will not
calculate or log the maximum
demands

Min. Outage
Duration

Minimum Outage
Duration, s

0-900 s

0

The minimum power outage
duration to apply the demand
forgiveness time

Test Mode

Test Mode

Energy LED Test

OFF (disabled)
ON (enabled)

Disabled

Setting this option puts the meter
into TEST mode

Pulse
Constant

Energy LED pulse
rate, Wh/impulse

0.01-0.25 Wh/imp

(100,000 – 4,000
imp/kWh)

0.10 Wh/imp
(10,000
imp/kWh)

Test LED pulse constant - the
amount of accumulated energy (in
secondary units) giving one pulse
via “WATT” and “VAR” LEDs

Data Scales

N/A

Volts Scale, V

60-600 V

144 V

The maximum voltage scale
allowed, in secondary volts. See

Data Scales

in Appendix G

N/A

Amps Scale, A

1.0 – 50.0

4A/20 A

The maximum current scale
allowed, in secondary amps. See

Data Scales

in Appendix G

Power Calculation Modes

The power calculation mode option allows you to change the
method for calculating reactive and apparent powers in
presence of high harmonics. The options work as follows: