Transformer/line loss compensation setup – E-Mon E-PS-S-HV-RTU User Manual
Page 79

Chapter 5 Configuring the PowerSmart Socket PQM
General Meter Setup
PowerSmart Socket Power Quality Meter
79
current. When a single test point is defined, it is applied over
the full operating range of the transformer.
The order in which you define the test points does not
matter. The meter will automatically arrange all data in a
correct order.
Check the Correction Enabled box to activate transformer
correction in the meter. You can also enable and disable
transformer correction from the front display (see
Device
Options and Mode Control
).
Transformer/Line Loss Compensation Setup
Loss compensation corrects the power and energy readings of
the meter when the metering point and point of billing are
physically separated by a power transformer or a power line.
Select General Setup from the Meter Setup menu, and then
click on the Transformer/Line Loss Compensation tab.
The available options are described in the following table.
Parameter
Options
Description
Metering and Location
Loss Compensation Enabled
Disabled, Enabled
Enables/disables loss compensation
Metering Point Location
Supply side, far
end,
Supply side,
transformer end,
Load side,
transformer end,
Load side, far end
Defines the location of the meter:
far end – near the supply source or near the load,
transformer end – near the power transformer.