E-Mon E-PS-S-HV-RTU User Manual
Page 114

Chapter 5 Configuring the PowerSmart Socket PQM
Configuring Recorders
114
PowerSmart Socket Power Quality Meter
neighboring parameters: when you open the “Group”
box for the next parameter, Power Software highlights
the same group as in your previous selection; if you
select this group again, Power Software automatically
updates the “Parameter” box with the following
parameter in the group.
4. Add the name for your data log file in the “Name” box.
It will appear in the data log reports.
5. Save your new setup to the device database, and send
it to the meter.
Factory Preset Data Log Files
Conventional Data Logs
Data log #1 and Data log #2 are factory preset for 15-min
periodic recording of the standard power quantities. You can
freely change the list of recorded parameters and the update
rate for both files.
Periodic recording data to these files is triggered by Setpoint
#1 that is linked to the meter clock. To change the periodic
rate at which data is recorded, change the time interval for
the MINUTE INTERVAL trigger in Setpoint #1 (See
Using
Control Setpoints
in Chapter 5).
Data Log #1
Data Log #1 is configured for recording 1-second phase
voltages, currents total harmonics, and total powers. The list
of parameters is shown in the following table.
Data Log #1
No.
Parameter
1
V1/V12
2
V2/V23
3
V3/V31
4
I1
5
I2
6
I3
7
Total kW
8
Total kvar
9
Total kVA
10
Total PF
11
V1/V12 THD
12
V2/V23 THD
13
V3/V31 THD
14
I1 THD
15
I2 THD
16
I3 THD
Data Log #2
Data Log #2 is configured for recording present voltage,
current and power demands, engineering (not billing) energy
counters, and 1-second neutral current and line frequency.
The list of parameters is shown in the following table.