Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Recorders

114

PowerSmart Socket Power Quality Meter

neighboring parameters: when you open the “Group”
box for the next parameter, Power Software highlights
the same group as in your previous selection; if you
select this group again, Power Software automatically
updates the “Parameter” box with the following
parameter in the group.

4. Add the name for your data log file in the “Name” box.

It will appear in the data log reports.

5. Save your new setup to the device database, and send

it to the meter.

Factory Preset Data Log Files

Conventional Data Logs

Data log #1 and Data log #2 are factory preset for 15-min
periodic recording of the standard power quantities. You can
freely change the list of recorded parameters and the update
rate for both files.

Periodic recording data to these files is triggered by Setpoint
#1 that is linked to the meter clock. To change the periodic
rate at which data is recorded, change the time interval for
the MINUTE INTERVAL trigger in Setpoint #1 (See

Using

Control Setpoints

in Chapter 5).

Data Log #1

Data Log #1 is configured for recording 1-second phase
voltages, currents total harmonics, and total powers. The list
of parameters is shown in the following table.

Data Log #1

No.

Parameter

1

V1/V12

2

V2/V23

3

V3/V31

4

I1

5

I2

6

I3

7

Total kW

8

Total kvar

9

Total kVA

10

Total PF

11

V1/V12 THD

12

V2/V23 THD

13

V3/V31 THD

14

I1 THD

15

I2 THD

16

I3 THD

Data Log #2

Data Log #2 is configured for recording present voltage,
current and power demands, engineering (not billing) energy
counters, and 1-second neutral current and line frequency.
The list of parameters is shown in the following table.