Configuring the daily tariff schedule – E-Mon E-PS-S-HV-RTU User Manual
Page 106

Chapter 5 Configuring the PowerSmart Socket PQM
Configuring Billing/TOU
106
PowerSmart Socket Power Quality Meter
Parameter
Options
Default
Description
Channel
None, Ch1-Ch6
None
Defines a measurement channel for multi-
meter energy metering. Not used for a
single self-metering channel if there are no
external sources. Set to Ch1 for internal
energy sources, and to Ch2 through Ch6 for
external sources in the event of multi-
channel energy metering.
Register Source List
Source
Input
None
kWh IMPORT
KWh EXPORT
kvarh IMPORT
kvarh EXPORT
kvarh Q1
kvarh Q2
kvarh Q3
kvarh Q4
kVAh TOTAL
kVAh IMPORT
kVAh EXPORT
DI1-DI10
None
Links an internal or external energy source
to the billing register.
Multiplier
0.001 to 100.000
1.000
The multiplication factor for the energy
source. Not effective for internal sources.
Target
Reg#1- Reg#10
None
Defines the target billing register for the
energy source. It is set automatically.
Configuring the Daily Tariff Schedule
To configure your daily tariff schedule, select Energy/TOU
from the Meter Setup menu, and then click on the TOU Daily
Profiles tab.
The daily profile setup allows you to specify the daily tariff
change points with a 15-minute resolution for 4 seasons
using 4 different daily schedules for each season.