Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Billing/TOU

106

PowerSmart Socket Power Quality Meter

Parameter

Options

Default

Description

Channel

None, Ch1-Ch6

None

Defines a measurement channel for multi-
meter energy metering. Not used for a
single self-metering channel if there are no
external sources. Set to Ch1 for internal
energy sources, and to Ch2 through Ch6 for
external sources in the event of multi-
channel energy metering.

Register Source List

Source
Input

None
kWh IMPORT

KWh EXPORT

kvarh IMPORT

kvarh EXPORT

kvarh Q1

kvarh Q2
kvarh Q3

kvarh Q4

kVAh TOTAL

kVAh IMPORT

kVAh EXPORT

DI1-DI10

None

Links an internal or external energy source
to the billing register.

Multiplier

0.001 to 100.000

1.000

The multiplication factor for the energy
source. Not effective for internal sources.

Target

Reg#1- Reg#10

None

Defines the target billing register for the
energy source. It is set automatically.

Configuring the Daily Tariff Schedule

To configure your daily tariff schedule, select Energy/TOU
from the Meter Setup menu, and then click on the TOU Daily
Profiles tab.

The daily profile setup allows you to specify the daily tariff
change points with a 15-minute resolution for 4 seasons
using 4 different daily schedules for each season.