E-Mon E-PS-S-HV-RTU User Manual

Page 9

Advertising
background image

Chapter 1 Introduction

PowerSmart Socket Power Quality Meter

9

Meter Features

Billing/TOU

Accuracy class 0.2 ANSI C12.20 (current class 10 and 20)

active energy and class 0.5 reactive energy polyphase static
meter

Time-of-Use, 10 billing energy and maximum demand

registers, 8 tariff rates, 4 seasons x 4 types of days, 8 tariff
changes per day

One-time easy programmable tariff calendar schedule,

programmable or calendar scheduled daylight savings switch
dates

Tariff switching options: automatic via a tariff calendar

schedule, external via communications or digital inputs

Configurable triggering an end of billing period: automatic

monthly,

local

via

the

front

display,

remote

via

communications

Automatic recording billing energy, maximum demand and

cumulative maximum demand registers for last 24 billing
periods

Automatic 120–day daily energy and maximum demand profile

Automatic 120-day/15-minute or 240-day/30-minute energy

load profile

Easy access to the three previous billing period data via the

front display

Dynamic instrument transformer correction; up to 8 test points

for both ratio and phase angle error correction for external PTs
and CTs

Power transformer/line loss compensation

Multi-functional Power Meter

High-accuracy 3-phase Power meter: true RMS volts and

amps, powers, power factors, unbalance, neutral current,
frequency

Demand Meter: amps, volts, harmonic demands, block and

sliding power demands

Harmonic Analyzer: up to 50th harmonic volts and amps;

fundamental volts, amps, power and power factor, phasor,
symmetrical components

Power Quality

EN 50160 Power Quality (PQ) recorder: onboard power quality

analyzer; programmable limits; EN 50160 power quality event
log, EN 50160 compliance statistics; EN 50160 harmonics
survey statistics

Power frequency, voltage variations, rapid voltage changes,

IEC 61000-4-15 flicker, voltage dips, interruptions, temporary
overvoltages, transient overvoltages, voltage unbalance, IEC
61000-4-7 harmonic and interharmonic voltage, mains
signaling voltage

Advertising
This manual is related to the following products: