Configuring digital inputs – E-Mon E-PS-S-HV-RTU User Manual

Page 90

Advertising
background image

Chapter 5 Configuring the PowerSmart Socket PQM

General Meter Setup

90

PowerSmart Socket Power Quality Meter

Configuring Digital Inputs

The PowerSmart Socket PQM has two embedded digital
inputs (DI1-DI2) and can provide one additional expansion
module with a total of 8 digital inputs (DI3 through DI10).
I/O numbers are automatically assigned to the inputs.

To configure the digital inputs, select General Setup from the
Meter Setup menu, and then click on the Digital Inputs tab.
Digital inputs that are not present in your meter are not
shown.

The available options are shown in the following table.

Parameter

Options

Default

Description

Pulse input mode PULSE MODE

KYZ MODE

PULSE
MODE

Pulse mode: either leading, or trailing
edge of the input pulse is recognized as
an event.
KYZ mode: both leading and trailing
edges of the input pulse are recognized
as separate events.

Pulse polarity

NORMAL (N.O.)

INVERTING
(N.C.)

NORMAL

Normal polarity: the open to closed
transition is considered a pulse.
Inverting polarity: the closed to open
transition is considered a pulse. It has no
meaning in KYZ mode where both
transitions are effective.

Debounce time

1-1000 ms

10 ms

The amount of time while the state of the
digital input should not change to be
recognized as a new state. Too low
debounce time could produce multiple
events on the input change.