Configuring communication protocols, Configuring modbus – E-Mon E-PS-S-HV-RTU User Manual

Page 131

Advertising
background image

Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Communication

PowerSmart Socket Power Quality Meter

131

Configuring Communication Protocols

This section describes how to customize protocol options for
use with your application software.

Configuring Modbus

Modbus Point Mapping

The PowerSmart Socket PQM provides 120 user assignable
registers in the address range of 0 to 119. You can re-map
any register available in the device to any assignable register
so that Modbus registers that reside at different locations
may be simply accessed using a single request by re-
mapping them to adjacent addresses.

Initially these registers are reserved and none of them points
to an actual data register.

To build your own Modbus register map:

1. From the Meter Setup menu select Protocol Setup and

click on the Modbus Registers tab.

2. Click on the Default button to cause the assignable

registers to reference the actual default device register
11776 (0 through 119 are not allowable register
addresses for re-mapping).