Configuring dnp3, Dnp options – E-Mon E-PS-S-HV-RTU User Manual
Page 132

Chapter 5 Configuring the PowerSmart Socket PQM
Configuring Communication
132
PowerSmart Socket Power Quality Meter
3. Type in the actual addresses you want to read from or
write to via the assignable registers. Refer to the
PowerSmart Socket PQM Modbus Reference Guide for
a list of the available registers. Note that 32-bit
Modbus registers should always start at an even
register address.
4. Click Send to download your setup to the device.
Configuring DNP3
DNP Options can be changed both via DNP3 and Modbus.
Refer to the PowerSmart Socket PQM DNP3 Reference guide
for information on the protocol implementation and a list of
the available data points.
DNP Options
From the Meter Setup menu select Protocol Setup and click
on the DNP Options tab.
The following table describes available DNP options. Refer to
the DNP3 Data Object Library document available from the
DNP User’s Group on the DNP3 object types.
Parameter
Options
Default
Description
Binary Inputs (BI)
Number of BI to Generate
events
0-64
3
21
The total number of BI change
event points for monitoring
Binary Input Object
Single-bit
With Status
Single-bit
The default BI object variation for
requests with qualifier code 06
when no specific variation is
requested