General meter setup, Basic meter setup, Using the front display – E-Mon E-PS-S-HV-RTU User Manual
Page 73: Using power software

Chapter 5 Configuring the PowerSmart Socket PQM
General Meter Setup
PowerSmart Socket Power Quality Meter
73
General Meter Setup
Basic Meter Setup
The Basic Setup provides the meter with basic information
about your electrical network.
Using the Front Display
Select Basic from the main menu. See
Viewing and Changing
Setup Options
in Chapter 3 for information on navigating in
menus.
See the table below for available options.
Using Power Software
Select General Setup from the Meter Setup menu.
The following table lists available meter configuration options.
Display Label
Parameter
Options
Default
Description
Basic Configuration
Wiring
Wiring Mode
See Table
below
4LN3
The wiring connection of the
device
PT Ratio
PT Ratio
1
1.0-6500.0
1.0
The phase potential
transformer’s primary to
secondary ratio
Nom. Voltage
PT Secondary (L-L)
Voltage
50-480 V
120 V
The nominal secondary line-to-
line voltage. Used as a
reference voltage for the
EN50160 evaluation.