Chapter 5 Configuring the PowerSmart Socket PQM

General Meter Setup

PowerSmart Socket Power Quality Meter

73

General Meter Setup

Basic Meter Setup

The Basic Setup provides the meter with basic information
about your electrical network.

Using the Front Display

Select Basic from the main menu. See

Viewing and Changing

Setup Options

in Chapter 3 for information on navigating in

menus.

See the table below for available options.

Using Power Software

Select General Setup from the Meter Setup menu.

The following table lists available meter configuration options.

Display Label

Parameter

Options

Default

Description

Basic Configuration

Wiring

Wiring Mode

See Table
below

4LN3

The wiring connection of the
device

PT Ratio

PT Ratio

1

1.0-6500.0

1.0

The phase potential
transformer’s primary to
secondary ratio

Nom. Voltage

PT Secondary (L-L)
Voltage

50-480 V

120 V

The nominal secondary line-to-
line voltage. Used as a
reference voltage for the
EN50160 evaluation.