Appendix h device diagnostic codes – E-Mon E-PS-S-HV-RTU User Manual
Page 231

Appendix H Device Diagnostic Codes
PowerSmart Socket Power Quality Meter
231
Appendix H
Device Diagnostic Codes
Diagnostic
Code
Display Message
Description
Reason
2
RAM/Data fault
RAM/Data error
Hardware failure
3
Watchdog reset
Hardware watchdog reset
Hardware failure
4
Sampling fault
DSP/Sampling fault
Hardware failure
5
CPU exception
CPU exception
Hardware failure
6
Run-time error
Run-time error
Hardware failure
7
SW watchdog reset
Software watchdog timeout Hardware failure
8
Power down
Power down
Loss of power
9
Device reset
Warm restart/Device reset
External restart via communications
or by firmware upgrade.
10
Configuration reset
Configuration reset
Corrupted setup data has been
replaced with the default
configuration.
11
RTC fault
RTC fault
The clock time has been lost. With
auto-reset: cleared automatically as
the clock is updated.
12
Configuration fault
Configuration fault
Factory, calibration or basic device
configuration data has been
corrupted.
13
Low battery
Battery low
Low lithium battery. With auto-reset.
Battery check or replacement is required.
14
Exp. memory fault
Expanded memory fault
Hardware failure
15
CPU EEPROM fault
CPU EEPROM fault
Hardware failure
18
Coprocessor fault
Coprocessor fault
Hardware failure
20
Library error
C Library error
Hardware failure
22
Task error
Task error
Hardware failure
24
IRIG-B No signal
IRIG-B signal lost
No IRIG-B signal from the GPS
master clock. With auto-reset:
cleared automatically when the
IRIG-B signal is detected.
25
IRIG-B Unlocked
IRIG-B time unlocked
The GPS master clock has lost the
satellite signal. With auto-reset:
cleared automatically when the
satellite signal is locked.
29
Motion/tilt sensor
Motion/tilt sensor
The meter has been moved or tilted.
See
Device Diagnostics
for more information on the
PowerSmart Socket PQM built-in diagnostics. See
Device
Diagnostics Display
in Chapter 3 and
Clearing Device
Diagnostics
in Chapter 6 on how to inspect and clear the
device diagnostics in your meter.