Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Recorders

118

PowerSmart Socket Power Quality Meter

2. Select a file type for your file.

3. Select the number of channels for simultaneous

recording in the file to define the file record size.

4. Select the maximum number of records you want to be

recorded in the file.

5. The number of records required to store a single

waveform series per event is defined as follows:

Number of Records per Series = Sampling Rate
(Samples per Cycle) x Number of Cycles per Event /
512

6. The total number of records you should allocate to

store the required number of events (series) is defined
as follows:

Number of Records = Number of Records per Series x
Number of Series

7. For example, to record 64-cycle waveforms sampled

at a rate of 32 samples per cycle, the number of
records required for one waveform series would be:

Number of Records per Series = (32 x 64)/512 = 4.

To allocate space sufficient to store 20 waveform
events (series), the waveform log file should be set up
for 4 x 20 = 80 records.

8. Click OK, and save your setup to the site database

and then send to the meter.

To configure the waveform duration, sampling rate and
channels to be recorded in the file:

1. Click on the file you wish to configure to highlight it

and then click “Setup Recorder”, or click on the
“Waveform Recorder” tab.