E-Mon E-PS-S-HV-RTU User Manual
Page 11

Chapter 1 Introduction
PowerSmart Socket Power Quality Meter
11
•
8 digital counters for counting pulses from external sources
and internal events
•
4 programmable timers from 1 cycle to 24 hours for periodic
recording and triggering operations on a time basis.
Time and Clock
•
High-accuracy real-time clock with a lithium backup battery
•
1-ms satellite-synchronized clock option (IRIG-B time-code
input)
•
SNTP clock synchronization option
•
1PPM or 1PPS clock synchronization option via a fast digital
input
•
One-time programmable or calendar scheduled daylight saving
time (DST) switch dates; configurable DST start and end time
Extended Security
•
3-level password security for protecting meter setups and
accumulated data from unauthorized changes
Display
•
Easy to read high contrast graphical 4-inch 320x240 pixel (1/4
VGA) LCD display with backlight
•
Multi-page data display with auto-scroll; time, billing,
instrumentation and service data
•
Menu-driven setups
Standard Digital I/O
•
Two embedded fast digital inputs with 1 ms scan time
•
One KYZ relay output
Expansion I/O slot
•
8DI I/O module with 8 opto-isolated digital inputs
•
6DO I/O module with 6 relay outputs – two electromechanical
EMR Form A relays and four solid state SSR Form C relays
•
4AO analog output module with 0-1mA, +/-1mA, 0-20mA and
4-20mA current output options
Memory
•
16 Mbyte flash memory for long-term billing, event, waveform
and data recording
Standard Communications
•
Front ANSI C12.18 optical serial communication port (Modbus
RTU/ASCII and DNP3 protocols)
•
Embedded serial RS-485 port (Modbus RTU/ASCII and DNP3
protocols)
•
Full speed USB 1.1 port (Modbus RTU protocol)