Chapter 2 Operating the
PowerSmart Socket PQM

Billing and Energy Metering

20

PowerSmart Socket Power Quality Meter

kWh net (Q1+Q4)-(Q2+Q3) - instrumentation

kvarh delivered (Q1+Q2)

kvarh received (Q3+Q4)

kvarh net (Q1+Q2)-(Q3+Q4) - instrumentation

kvarh Q1, Q2, Q3, Q4 quadrants

kVAh delivered (Q1+Q4)

kVAh received (Q2+Q3)

kVAh total (Q1+Q2+Q3+Q4)

Energy Measurement Channels

The PowerSmart Socket PQM uses two independent current
channels for high-accuracy energy measurements and for
conventional high-range instrumentation. They provide
different gain and measurement ranges as necessary for
billing accuracy energy metering and for power quality and
fault monitoring.

1-second currents and powers provided by the meter and the
corresponding engineering display readings are taken from
the energy measurement channel. They begin measurements
from 5 mA starting currents and up to 20 A RMS with 5 A
secondaries,

while

instrumentation

currents

provide

measurements up to 50 A RMS.

Energy Counters

The PowerSmart Socket PQM provides instrumentation
energy and billing energy metering. Both use the same
energy measurement circuitry as a source input for
accumulation energies but operate independently.

Energy counters have a nine-digit kWh resolution with one
decimal place by default. You can set the energy counters to
have fewer digits by changing the default energy roll value in
your meter (see

Device Options and Mode Control

in Chapter

5).

Billing energy registers have the same resolution as
instrumentation energy counters.

Billing Energy Registers

The PowerSmart Socket PQM has 10 fully programmable
billing energy registers that can be linked to any internal
energy source or to any external pulse source that delivers
pulses through the device digital inputs.

Any of energy registers can provide either a single-tariff
energy accumulation or be individually linked to the TOU
system providing both total and multi-tariff energy billing.

See

Configuring Billing/TOU

in Chapter 5 on how to configure

the meter billing registers and tariff schedule for your
application.