Chapter 5 Configuring the PowerSmart Socket PQM

Configuring Communications

66

PowerSmart Socket Power Quality Meter

Display

Label

Parameter

Options

Default

Description

Protocol

Communication
protocol

Modbus RTU,
Modbus ASCII,

DNP3,

IEC 62056-21

IEC 62056-21
(COM1)
Modbus RTU
(COM3-4)

The communications
protocol for the port

Interface

Port interface

RS232, RS485,
IR, GPRS

IR (COM1)
GPRS (COM2)

RS485 (COM3-
4)

Not changeable;
automatically detected by
the meter

Address

Device address Modbus: 1-247

DNP3: 0-65532

IEC 62056-21:
0-65532

1

Device network address

Baud Rate

Baud rate

COM1: 300-
19200 kbps,
COM2-4: 300-
115.2 kbps

19.2 kbps

The port baud rate

Data/Parity

Data format
and parity

7E, 8N, 8E

8N

7E data format should not
be used with the Modbus
RTU and DNP3 protocols

Send Delay

Response delay 0-1000 ms

5 ms

The minimum time after the
last request character is
received to start the
transmission.

Chr.Timeout

Character
timeout

0-1000 ms

4 ms

The maximum time the line
is allowed to idle before
closing a connection in the
Modbus RTU and DNP3
protocols

The meter automatically detects replaceable communication
modules and does not allow you to change the baud rate and
data format for the Dial-up GSM/GPRS modem.