Chapter 2 Operating the
PowerSmart Socket PQM

Meter Security

18

PowerSmart Socket Power Quality Meter

noise in the region of the device. If the device continuously
resets itself, contact your local distributor.

Device Fault Alarm

The PowerSmart Socket PQM provides a global "DEVICE
FAULT" event flag that is asserted all the time while one of
the diagnostic events exists. It can be monitored via a
setpoint (see

Using Control Setpoints

in Chapter 5) to give a

fault indication through a relay output. If the alarm relay is
programmed for failsafe mode using inverting polarity, then
its normally closed contacts will be open if either the meter
looses power or a device fault occurs.

Meter Security

The PowerSmart Socket PQM provides 3-level password
security for protecting meter setups and accumulated data
from unauthorized changes. Meter readings are not software
protected.

Access to particular setup and control items is granted
depending on the security level of the password you entered.
The passwords can be 1 to 8 digits long.

The PowerSmart Socket PQM is also provided with the
security jumper located on the main CPU board under the
meter cover. Removing the security jumper grants a full
access to the meter settings and permits clearing the billing
data registers and billing data profile files (see

Clearing Billing

Data

).

The following table shows the meter security levels and user
access rights.

Password

Security Level

Access Rights

Password 1

Low

Reset of billing and engineering maximum
demands, and device diagnostics.

Meter clock update.
Display setup.

Password 2

Medium

TEST mode.

Reset of meter and battery operation time
counters, failure counters and pulse counters.

Communications setup.

I/O operation setup and control.

Memory and recorders setup.

Billing/TOU system setup.

Password 3

High

(Administration

level)

Meter passwords setup.
Basic device setup.

Device energy and power options setup.

Reset of conventional log files.

The meter is primarily shipped with all passwords preset to 9
at the factory. It is highly recommended that you change the
factory set passwords as fast as possible. See

Configuring

Meter Passwords

in Chapter 5 on how to change passwords in

your meter.