E-Mon E-PS-S-HV-RTU User Manual
Page 135

Chapter 5 Configuring the PowerSmart Socket PQM
Configuring Communication
PowerSmart Socket Power Quality Meter
135
The factory-set Class 0 point ranges are shown in the picture
below.
Configuring DNP Event Classes
The PowerSmart Socket PQM generates object change events
for any static analog input, binary input, and binary counter
point when a corresponding point either exceeds a predefined
threshold, or the point status changes. A total of 64 change
event points are available for monitoring.
Object change events are normally polled via DNP Class 1,
Class 2 or Class 3 requests. You can link any change event
point to any event class upon the event priority. Refer to the
PowerSmart Socket PQM DNP3 Reference Guide for more
information on polling event classes via DNP.
A change event point index is normally the same as for the
corresponding static object point. To use independent
numeration for event points, enable re-mapping event point
indices via DNP Options setup (see above) so they start with
index 0.
Define a separate event setpoint for each static object point
to be monitored for change events. To view or change the
factory-set DNP event setpoints, select Protocol Setup from
the Meter Setup menu and click on the DNP Event Setpoints
tab.