Data type -3, System web page overview – IDEC MicroSmart Pentra User Manual

Page 111

Advertising
background image

W

EB

S

ERVER

CPU M

ODULE

U

SER

S

M

ANUAL

FC9Y-B1278

12-3

12: W

EB

S

ERVER

System Web Page Overview

The system web page of the Web server CPU module consists of the following files.

/system/index.html: The PLC status can be monitored. This is also the top page of the system web page.
/system/batch_monitor.html: Batch monitor to monitor a group of data registers.
/system/custom_monitor.html: Custom monitor to register and monitor a maximum of 30 data registers or internal
relays.
/system/device_read.cgi: CGI for reading device data used by JavaScript
/system/device_write.cgi: CGI for writing device data used by JavaScript

Data Type

The following data types can be specified in batch monitor, custom monitor, or user web pages when the system library
parts are used.

Note: BIN-B is used in the custom monitor when internal relay is monitored. 0000 is OFF and 0001 is ON.

Data Type

Data Size

Valid Range

HEX-W

Hexadecimal

1 word

0000 to FFFF

HEX-D

Hexadecimal

2 words

00000000 to FFFFFFFF

DEC-W

Decimal

1 word

0 to 65535

DEC-I

Decimal

1 word

-32768 to 32767

DEC-D

Decimal

2 words

0 to 4294967296

DEC-L

Decimal

2 words

-2147483648 to 2147483647

DEC-F

Decimal

2 words

IEEE754 format. Digits is 7.

BIN-B

Binary

1 word

0000 or 0001 (Note)