Input Wiring

Output Wiring

• Separate the input wiring from the output line, power line, and motor line.

• Use proper wires for input wiring.

All-in-one type CPU modules:

UL1015 AWG22 or UL1007 AWG18

Slim type CPU and I/O modules: UL1015 AWG22

Caution

• If output relays or transistors in the Web Server CPU or output modules should fail, outputs may remain on

or off. For output signals which may cause heavy accidents, provide a monitor circuit outside the Web
server CPU module.

• Connect a fuse to the output module, selecting a fuse appropriate for the load.

• Use proper wires for output wiring.

All-in-one type CPU modules:

UL1015 AWG22 or UL1007 AWG18

Slim type CPU and I/O modules: UL1015 AWG22

• When equipment containing the Web server CPU module is intended for use in European countries, insert

an IEC 60127-approved fuse to each output of every module for protection against overload or short-
circuit. This is required when equipment containing the Web server CPU module is destined for Europe.